30 Amp Electric Models - Hearth
When
choosing a site for an Aga there are a number of factors
to consider which will influence its positioning.
The
Aga also has to be installed in accordance with current
legislation, such as Building Regulations and Industry
Codes of Practice.
Therefore
we strongly recommend a free Home Survey
Floor/Hearth/Plinth.
The floor must be strong enough to carry the weight
of the Aga:
2 Oven
708kg (14cwt)
4 Oven 842kg (16.5cwt)
Where an
Aga Electric or Gas Module is attached add 129kg (2.5cwt)
The hearth
must be non combustible for a thickness of at least 50mm
A raised
plinth is not essential, and there is no reason why an
Aga shouldnt sit on the normal floor (providing it
meets the above criteria).
If a
higher working position is preferred, or the finished
height needs to match adjacent work surfaces, then a cast
concrete slab, usually 50mm thick, is the answer. The
slab dimensions should be the same as the base of the Aga
2 oven
987 x 679mm
4 oven 1487 x 679mm
The 679
dimension can be reduced slightly if the front of the
plinth is to be tiled.
Whatever
type of hearth is chosen, it must be absolutely level in
all directions.
Heat to
Room.
The Aga releases a gentle warmth into the kitchen,
which is not likely to give rise to any problems, unless
the room is exceptionally small or poorly ventilated. The
actual output varies slightly from model to model and in
accordance with the method of installation. An average
heat contribution to the room of 1.25 kW/hr should be
allowed.
Dimensions:
Maximum
depth over handrail etc 756mm
Maximum width, 2 oven 987mm, 4 oven 1487mm (see note
below)
Maximum height with lnsulating lids open 1330mm (see
note below)
Clearances.
In most case, work units can be brought right up to
the sides of the Aga, without the risk of damage from
heat. Work tops should however stop short of the Aga top
plate and not actually touch it. A gap of 3mm each side of the top plate
is important to enable the cooker top plate to be removed.Any slight gap can be
filled with a silicone sealant.
If the
surrounding walls are to be tiled, then this must be done
before the Aga is installed, as the tiles must be taken
down below the Aga top plate level, not finish above it.
The rear
wall must be non combustible for at least 25mm In a
timber framed building, protection can be provided as
shown below.

In a
recess situation, If the adjacent right-hand wall
protrudes forward beyond the front of the Aga, then an
additional width clearance is required of 116mm on the
right hand side, to allow the oven door to be opened
sufficiently, as shown below.

If the Aga
is to be installed in a brick recess, then the minimum
clearances should be increased by at least 10mm on either
side, to allow for the walls being out of square and also
for the natural dimensional variations found in castings.
At least
60mm clearance should be allowed above the insulating
covers in their vertical, open position.
|