Gas Fired Models - Hearth
When
choosing a site for an Aga there are a number of factors
to consider which will influence its positioning.
Flue/Chimney.
May require the Aga to be close to an existing chimney or
against an outside wall. See separate sheet on
flues/chimney/ventilation.
Floor/Hearth/Plinth.
The floor must be strong enough to carry the weight
of the Aga, typically:
2 Oven
406kg (8cwt)
3 Oven 477kg (9.4cwt)
4 Oven 584kg (10cwt)
Where an
Aga Electric or Gas Module is attached add 129kg (2.5cwt)
The hearth
must be non combustible for a thickness of at least12mm
A raised
plinth is not essential, and there is no reason why an
Aga shouldnt sit on the normal floor ( providing it
meets the above criteria) If a higher working position is
preferred, or the finished height needs to match adjacent
work surfaces, then a cast concrete slab, usually 50mm
thick, is the answer.
The slab
dimensions should be the same as the base of the Aga
2 & 3 oven
987 x 679m
4 oven 1487 x 679
The 679
dimension can be reduced slightly if the front of the
plinth is to be tiled.
Alternatively, there
are several purpose made plinths available to suit the parent Aga, the hot cupboard (for the 4 oven Aga) and the gas and electric Modules.
These raise the height by either 65mm or 85mm.
Whatever
type of hearth is chosen, it must be absolutely level in
all directions.
Clearances.
In most case, work units can be brought right up to
the sides of the Aga, without the risk of damage from
heat. Work tops should however stop short of the Aga top
plate and not actually touch it. A gap of 3mm each side of the top plate
is important to enable the cooker top plate to be removed. Any slight gap can be
filled with a silicone sealant.
If the
surrounding walls are to be tiled, then this must be done
before the Aga is installed, as the tiles must be taken
down below the Aga top plate level, not finish above it.
The rear
wall must be non combustible for at least 25mm thickness.
In a
recess situation, if the adjacent right-hand wall
protrudes forward beyond the front of the Aga, then an
additional width clearance is required of 116mm on the
right hand side, to allow the oven door to be opened
sufficiently. This 116mm clearance is also required to the left hand
side in the case of the 3 oven Aga, unless a module is being installed
as well.
If the Aga
is to be installed in a brick recess, then the minimum
clearances should be increased by at least 10mm on either
side, to allow for the walls being out of square and also
for the natural dimensional variations found in castings.
At least
60mm clearance should be allowed above the insulating
covers in their vertical, open position.
Aga
Dimensions:
Maximum
depth over handrail etc 756mm
Maximum width, 2 and 3 oven 987mm, 4 oven 1487mm (see note
above)
Maximum height with insulating lids open 1330mm (see
note above)
|