Oil Fired Models - Hearth
Flue/Chimney.
May require the Aga to be close to an existing
chimney or against an outside wall. See separate sheets
on flues/chimney/ventilation.
Floor/Hearth/Plinth.
The floor must be strong enough to carry the weight
of the Aga, typically:
2 Oven
406kg (8cwt)
3 Oven 477kg (9.4cwt)
4 Oven 584kg (11.5cwt)
Where an
Aga Electric or Gas Module is attached add 129kg (2.5cwt)
The hearth
must be non combustible for a thickness of at least 12mm
A raised
plinth is not essential, and there is no reason why an
Aga shouldnt sit on the normal floor ( providing it
meets the above criteria).
If a
higher working position is preferred, or the finished
height needs to match adjacent work surfaces, then a cast
concrete slab, usually 50mm thick, is the answer. The
slab dimensions should be the same as the base of the
Aga:
2 & 3 oven
987 x 679mm
4 oven 1487 x 679mm
The 679
dimension can be reduced slightly if the front of the
plinth is to be tiled.
Alternatively, there are
also three purpose made plinths available to suit 2 and 3 oven gas or
oil fired Aga, the hot cupboard (for the 4 oven Aga) and another for the
gas and electric Modules.
Whatever
type of hearth is chosen, it must be absolutely level in
all directions.
Clearances.
A 2 or 4 oven oil-fired Aga
requires an oil control valve to be fitted on its left or
right hand side. (Note. If an Aga module is also
installed then the valve must be fitted to the R.H side)
This valve requires easy access for adjustment and
servicing, therefore if the Aga is to be installed in a
recess, increased width clearances are needed,
significantly larger than the actual Aga dimensions.
In particular, please ensure that the oil control box mounted to the
side of the Aga, the fire valves, isolation valves and fittings are
always accessible to ensure that they can be accessed for future service
and maintenance.
In this
view the oil control valve is shown on the left hand side
of a 2 oven cooker. Total Clearance required = 1303mm. (i.e. Aga width 987 mm + oil valve access 200 mm + door
opening clearance 116 mm).
If the
right hand wall does not protrude forward beyond the
front of the Aga, then there is no need for a clearance
here. In this case the Total clearance required would be
1187mm. (i.e. Aga width 987mm + valve clearance 200mm).
Had the
valve been installed on the right hand side, there would
be no need for a gap on the left, therefore the Total
Clearance required = 1187mm, whether or not the right
hand wall extends forward.
For a 4
oven Aga, add 500mm to cooker width in the above
calculations.
Note that the diesel and 3 oven models do not have an oil control
valve.
If the Aga
is to be installed in a tight brick recess, then the
minimum clearances should be increased by at least 10mm
on either side, to allow for the walls being out of
square and also for the natural dimensional variations
found in castings.
If the Aga
is not going into a tight recess, but merely between
kitchen work units, then there is no reason why the units
cannot be brought up to the side of the Aga, with the Oil
control valve being actually located in the cupboard, the
latter having a false wall. Zero clearances are then
required.
Under some
special circumstances, it may be possible to site the oil
control valve remotely from the Aga, but the distance
from the burner must not exceed 3 metres.
Work tops
should however stop short of the Aga top plate and not
actually touch it. A gap of 3mm each side of the top plate is important to
enable the cooker top plate to be removed. Any slight gap can be filled with a
silicone sealant.
If the
surrounding walls are to be tiled, then this must be done
before the Aga is installed, as the tiles must be taken
down below the Aga top plate level, not finish above it.
The rear
wall must be non combustible for at least 25mm thickness.
At least
60mm clearance should be allowed above the insulating
covers in their vertical, open position.
Dimensions
Aga Dimensions:
Maximum
depth over handrail etc 756mm
Maximum width, 2 oven 987mm, 4 oven 1487mm (see note
above)
Maximum height with insulating lids open 1330mm (see
note above)
Heat to
Room.
The Aga releases a gentle warmth into the kitchen,
which is not likely to give rise to any problems, unless
the room is exceptionally small or poorly ventilated. The
actual output varies slightly from model to model and in
accordance with the type of flue system chosen. An
average contribution to the room of 1 kW/hr should be
allowed.
|