Oil Fired Models - Flues
An Oil-fired Aga requires some form
of flue or chimney system, so as to safely remove the
natural products of combustion, at the same time taking
cooking smells and steam from the ovens.
For the Aga to work properly, the
chimney must be constructed of the the appropriate
materials and rise to a satisfactory height, whilst
complying with current legislation, such as the Building
Regulations.
The need for access to a chimney
will probably dictate the position chosen for the Aga,
and we would strongly advise that your local Aga
Distributor be asked to carry out a survey of the
proposed site.
Two main chimney arrangements are
available (see illustration below):
1.To use a masonry chimney,
suitably lined with an appropriate material and
terminating at a height above the main roof ridge. An
original, rigid lining would be of at least 150 mm
diameter, but if a stainless steel flexible lining is
used, this may be 125mm diameter.
2.Where no convenient chimney
exists, it is possible to use a twin walled, factory
insulated, prefabricated, stainless steel chimney system,
the internal diameter of which should be at least 127mm.
3. A cleaning access door is to be provided on the
first flue bend fitted adjacent to the Aga, or in a similar convenient
position so as to clean back towards the Aga.

Whichever arrangement is chosen
there are several requirements common to both:
No flue sharing with other
appliances
Bends to be kept to a minimum and
must not be less than 135 degrees from the vertical.
For aesthetic reasons, black
vitreous enamelled, single skin, cast iron pipe may be
used to connect between the Aga and the main chimney. The
pipe will be 100mm diameter, rising vertically from the
top of the Aga, before bending at 45 degrees into the
chimney, where necessary. Single skin pipe must not
extend outside of the kitchen area.
Alternatively, it is sometimes
possible to use a rear connection from the Aga (2 and 4 oven kerosene
models only), horizontally through the rear wall and into
a chimney situated immediately behind. The horizontal
pipe must be no longer than 150mm, I.e. the thickness of
a single brick.
The flue or chimney must terminate
above the main roof ridge.
In most cases a simple rain-cap
should be sufficient as a terminal, but occasionally a
venturi type cowl may be helpful, to overcome the effects
of intermittent down draught, caused by the proximity of
trees or other topographical features. Consider using the
Vedette or O-H cowls.
Electrically powered fanned flues are not recommended,
due to the possible ill-effects in a power cut situation.
The Aga oil burner requires a low,
but consistent negative draught to function correctly.
High up-draughts, experienced in windy or tall chimney
locations, can adversely affect performance. Where this
is likely to occur, we recommend an automatic
Draught Stabiliser, to maintain the draught
at the appropriate level. This is fitted in the flue
pipe, adjacent to, and in the same room as the Aga.
|